Schneider Electric TeSys F Contactor, 3P, 3-NO, AC3, 440V, 115A, 110V AC Coil
Quick Overview
Range: TeSys
Product or component type: Contactor
Contactor application: Motor control
Poles: 3P
TeSys F contactor,3 poles (3NO),115A/690V AC-3,for motor applications up to 55kW@400V. It provides a low sealed consumption 110V 40-400Hz AC coil,bolt terminals for bars or cables with lugs. For high operating rates until 2400 cycles/hour and environments until 55°C,it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC,UL,CSA,CCC,EAC,Marine),Green Premium compliant (RoHS/REACh)
| Specifications | |
Main | |
| Range | TeSys |
| Range of product | TeSys F |
| Product or component type | Contactor |
| device short name | LC1F |
| contactor application | Motor control |
| Resistive load | |
| utilisation category | AC-4 |
| AC-1 | |
| AC-3 | |
| Poles description | 3P |
| [Ue] rated operational voltage | <= 690 V AC 50/60 Hz |
| <= 460 V DC | |
| [Uc] control circuit voltage | 110 V AC 40...400 Hz |
| [Ie] rated operational current | 200 A (at <40 °C) at <= 440 V AC-1 |
| 115 A (at <55 °C) at <= 440 V AC-3 | |
| Complementary | |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ith] conventional free air thermal current | 200 A (at 40 °C) |
| Rated breaking capacity | 920 A conforming to IEC 60947-4-1 |
| [Icw] rated short-time withstand current | 1100 A 40 °C - 10 s |
| 640 A 40 °C - 30 s | |
| 520 A 40 °C - 1 min | |
| 400 A 40 °C - 3 min | |
| 320 A 40 °C - 10 min | |
| Associated fuse rating | 125 A aM at <= 440 V |
| 200 A gG at <= 440 V | |
| Average impedance | 0.37 mOhm - Ith 200 A 50 Hz |
| [Ui] rated insulation voltage | 1000 V conforming to IEC 60947-4-1 |
| 1500 V conforming to VDE 0110 group C | |
| Power dissipation per pole | 15 W AC-1 |
| 5 W AC-3 | |
| Overvoltage category | III |
| power pole contact composition | 3 NO |
| Motor power kW | 55 kW at 380...400 V AC 50/60 Hz (AC-3) |
| 59 kW at 415 V AC 50/60 Hz (AC-3) | |
| 59 kW at 440 V AC 50/60 Hz (AC-3) | |
| 75 kW at 500 V AC 50/60 Hz (AC-3) | |
| 80 kW at 660...690 V AC 50/60 Hz (AC-3) | |
| 30 kW at 220...230 V AC 50/60 Hz (AC-3) | |
| 18.5 kW at 400 V AC 50/60 Hz (AC-4) | |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) |
| Drop-out: 0.2...0.55 Uc 40...400 Hz (at 55 °C) | |
| Mechanical durability | 10 Mcycles |
| Inrush power in VA | 770 VA, 40...400 Hz cos phi 0.9 (at 20 °C) |
| Hold-in power consumption in VA | 8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C) |
| Maximum operating rate | 2400 cyc/h 55 °C |
| Operating time | 35 ms closing (at Uc) |
| 130 ms opening (at Uc) | |
| Connections - terminals | Power circuit: bar 2 cable(s) - busbar cross section: 20 x 3 mm |
| Power circuit: lugs-ring terminals 1 cable(s) 95 mm² | |
| Power circuit: connector 1 cable(s) 95 mm² | |
| Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end | |
| Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end | |
| Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end | |
| Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end | |
| Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end | |
| Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end | |
| Power circuit: bolted connection | |
| Tightening torque | Power circuit: 10 N.m |
| Control circuit: 1.2 N.m | |
| mounting support | Plate |
| Heat dissipation | 5.9…7.2 W |
| standards | EN 60947-4-1 |
| IEC 60947-1 | |
| IEC 60947-4-1 | |
| EN 60947-1 | |
| JIS C8201-4-1 | |
| product certifications | CCC |
| CB | |
| RMRoS | |
| LROS (Lloyds register of shipping) | |
| DNV | |
| ABS | |
| RINA | |
| UL | |
| BV | |
| UKCA | |
| Compatibility code | LC1F |
| Control circuit type | AC at 40...400 Hz |
| Environment | |
| IP degree of protection | IP2X front face with shrouds conforming to IEC 60529 |
| IP2X front face with shrouds conforming to VDE 0106 | |
| Protective treatment | TH |
| Ambient air temperature for operation | -40…60 °C |
| Ambient air temperature for storage | -60…80 °C |
| Permissible ambient air temperature around the device | 60…70 °C at Uc |
| height | 162 mm |
| Width | 163.3 mm |
| Depth | 171 mm |
| Operating altitude | 3000 m without derating |
| Net weight | 3.43 kg |
| Weight | 3.430000 |
|---|---|
| Brand | Schneider Electric |
| Model | LC1F115F7 |
| Depth [cm] | 17.1 |
| Width [cm] | 16.33 |
| Height [cm] | 16.2 |
| Range | Tesys D |
| Family | PPCTR |
Write Your Own Review