Residual current circuit breaker, 2 poles, 63 A, class AC 30mA
Poles description: 2P
Earth-leakage protection class: Type AC
[In] rated current: 63 A
Earth-leakage sensitivity: 30 mA
The Residual Current Circuit Breaker (RCCB) is a fundamental component for electrical safety, and this 2-pole RCCB, with a current rating of 63 A and Class AC, is designed to provide that protection. Whether for residential or commercial applications, it ensures the safety of electrical circuits.
Key Features:
Two Poles: This RCCB provides protection for two circuits, making it suitable for various setups.
High Current Rating: With a 63 A current rating, it can handle substantial electrical loads.
Class AC: Designed for both residential and commercial applications, offering versatility.
30mA Sensitivity: Ensures effective protection against electrical faults.
Reliable Performance: Schneider Electric products are known for their reliability and performance, and this RCCB is no exception.
The Residual Current Circuit Breaker (RCCB) plays a crucial role in preventing electrical hazards and ensuring the safety of people and property. Schneider Electric's 2-pole RCCB provides peace of mind and dependable electrical protection, making it an ideal choice for various applications.
| Specifications | |
Main | |
| Range | Domae |
| Product or component type | Residual current circuit breaker (RCCB) |
| Device short name | RCCB |
| Poles description | 2P |
| Earth-leakage protection class | Type AC |
| Complementary | |
| Neutral position | Left |
| device location in system | Outgoer |
| [In] rated current | 63 A |
| Network type | AC |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 230 V AC 50/60 Hz conforming to IEC 61008 |
| Residual current tripping technology | Electromechanical |
| Earth-leakage sensitivity | 30 mA |
| earth-leakage protection time delay | Instantaneous |
| Rated breaking and making capacity | Im = 630 A |
| Rated conditional short-circuit current | 6 kA 63 A |
| [Ui] rated insulation voltage | 440 V |
| [Uimp] rated impulse withstand voltage | 4 kV |
| control type | Toggle |
| Mounting mode | Fixed |
| mounting support | 35 mm symmetrical DIN rail |
| Connection pitch | 18 mm between phase and neutral |
| 9 mm pitches | 4 |
| height | 81 mm |
| Width | 36 mm |
| Depth | 76 mm |
| Connections - terminals | Tunnel type terminals (downstream) 25 mm² flexible |
| Tunnel type terminals (downstream) 35 mm² rigid | |
| Tunnel type terminals (upstream) 25 mm² flexible | |
| Tunnel type terminals (upstream) 35 mm² rigid | |
| Environment | |
| standards | IEC 61008 |
| Pollution degree | 2 |
| Tropicalisation | 2 conforming to IEC 61008 |
| Operating altitude | 2000 m |
| Ambient air temperature for operation | -5…40 °C |
| Ambient air temperature for storage | -40…60 °C |
| Weight | 0.220000 |
|---|---|
| Brand | Schneider Electric |
| Model | 16791 |
| Depth [cm] | 7.6 |
| Width [cm] | 3.6 |
| Height [cm] | 8.1 |
| Range | Domae RCCB |
| Family | HDCFD |
| Type | Residual current circuit breaker (RCCB) |
| Poles | 2P |
| [In] Rated Current | 63 A |