Compact NSX100N Circuit Breaker, 50kA at 415VAC, 3 Poles, TMD Trip Unit, 25A

In stock
SKU
C10N3TM025
Special Price EGP 12,467 Regular Price EGP 18,890
Compact NSX100N Circuit Breaker, 50kA at 415VAC, 3 Poles, TMD Trip Unit, 25A is available to buy in increments of 1
Quick Overview

Product or component type: Circuit breaker
Device application: Distribution
Number of poles: 3P
[in] Rated Current: 25 A at 40 °C

Introducing the Schneider Electric Compact NSX100N Circuit Breaker, a high-performance solution for circuit protection. Engineered to ensure the safety and efficiency of your electrical systems, this circuit breaker offers robust protection capabilities, making it suitable for a variety of applications.

 

Key Features:

High Breaking Capacity: With an impressive 50kA breaking capacity at 415VAC, this circuit breaker can handle fault currents, enhancing the safety of your electrical circuits.

3 Poles: The 3-pole configuration adds versatility to your electrical system, making it suitable for various applications and installations.

TMD Trip Unit: Equipped with a TMD trip unit, this circuit breaker offers reliable protection with adjustable settings, ensuring precise fault detection and response.

25A Rating: The 25A rating allows this circuit breaker to handle moderate electrical loads while providing reliable protection.

Technical Specifications:

Breaking Capacity: 50kA at 415VAC

Poles: 3

Trip Unit Type: TMD

Current Rating: 25A

Specifications 

Main

 
RangeComPacT new generation
Product nameComPacT NSX new generation
Device short nameNSX100N
Product or component typeCircuit breaker
Device applicationDistribution
Poles description3P
Protected poles description3D
[In] rated current25 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
Network typeAC
Network frequency50/60 Hz
Suitability for isolationYes conforming to EN/IEC 60947-2
utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Performance levelN 50 kA 415 V AC
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Trip unit protection functionsLI
control typeToggle
Circuit breaker mounting modeFixed
Complementary 
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability50000 cycles
Electrical durability50000 cycles at 440 V In/2
 30000 cycles at 440 V In
 20000 cycles at 690 V In/2
 10000 cycles at 690 V In
Power dissipation per pole4.01 W
mounting supportBackplate
Mounting positionHorizontal and vertical
 Flat on the back
Upside connectionFront
downside connectionFront
Connection pitch35 mm
Protection typeL : for overload protection (thermal)
 I : for short-circuit protection (magnetic)
Trip unit rating25 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120…400 s at 1.5 x In
 15 s at 6 x Ir
Instantaneous protection pick-up adjustment type IiFixed
[Ii] instantaneous protection pick-up adjustment range300 A
earth-leakage protectionWithout
Number of slots for electrical auxiliaries5 slot(s)
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
Net weight2.05 kg
Environment 
standardsEN/IEC 60947
product certificationsCCC
 EAC
 Marine
Overvoltage categoryClass II
Electrical shock protection classClass II
Pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-50…85 °C
Relative humidity0…95 %
Operating altitude0...2000 m without derating
 2000 m...5000 m with derating

 

 

 

 

More Information
Weight2.050000
BrandSchneider Electric
ModelC10N3TM025
Device ApplicationDistribution
Depth [cm]8.6
Width [cm]10.5
Height [cm]16.1
RangeNSX
FamilyPPCCB
TypeCircuit Breaker
Poles3P
[In] Rated Current25 A at 40 °C
0
Rating:
0% of 100
Write Your Own Review
You're reviewing:Compact NSX100N Circuit Breaker, 50kA at 415VAC, 3 Poles, TMD Trip Unit, 25A
Your Rating
WhatsApp Chat WhatsApp Chat