Circuit breaker EasyPact CVS160B, 25 kA at 415 VAC, 160 A rating thermal magnetic TM-D trip unit, 3P 3d
Numbers of poles: 3P
[In] rated current: 160 A at 40 °C
Network type: AC
EasyPact CVS160B is a 3 poles 3d fixed circuit breaker with a high level of performance and cost-saving functionality. It is an optimal choice for small and medium-sized buildings protection applications. The breaking capacity (Icu) is 25kA rms at 415VAC 50/60Hz. The operational voltage is 440VAC 50/60Hz. This product embeds a 160A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection.
Specifications:
Main | |
Range | EasyPact |
Range of product | EasyPact CVS100...250 |
Product name | EasyPact CVS |
Device short name | CVS160B |
product or component type | Circuit breaker |
Device application | Distribution |
poles description | 3P |
Protected poles description | 3D |
Earth leakage protection (Vigi add on) | Without |
[In] rated current | 160 A at 40 °C |
Network type | AC |
Utilisation category | Category A |
[Icu] Breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
Trip unit name | TM-D |
Trip unit technology | Thermal-magnetic |
Trip unit rating | 160 A at 40 °C |
Protection type | Overload protection (thermal) |
Short-circuit protection (magnetic) | |
Complementary | |
[Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
Network frequency | 50/60 Hz |
Breaking capacity code | B |
[Ics] rated service breaking capacity | 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 | |
Mechanical durability | 25000 cycles |
Electrical durability | 12000 cycles 415 V In conforming to IEC 60947-2 |
Control type | Toggle |
Thermal protection adjustment range | 112…160 A |
Long time pick-up adjustment type Ir | Adjustable |
Long time pick-up adjustment range | 0.7...1 x In |
Long time delay adjustment type | Fixed |
Instantaneous pick-up adjustment type Ii | Fixed |
instantaneous pick-up adjustment range | 1250 A |
Contact position indicator | Yes |
mounting support | Backplate |
mounting mode | Fixed |
Upside connection | Front |
downside connection | Front |
Connections - terminals | Screw connection |
Connection pitch | 35 mm |
Compatibility code | CVS160 |
Width | 105 mm |
Depth | 86 mm |
Height | 161 mm |
net weight | 1.5 kg |
Environment | |
Standards | IEC 60947-2 |
EN 60947-2 | |
Product certifications | GOST |
IEC | |
Electrical shock protection class | Class II |
Pollution degree | 3 conforming to IEC 60664-1 |
IP degree of protection | IP40 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -50…85 °C |
Weight | 1.500000 |
---|---|
Brand | Schneider Electric |
Model | LV516303 |
Depth [cm] | 8.6 |
Width [cm] | 10.5 |
Height [cm] | 16.1 |
Range | EasyPact |
Family | PPCCB |
Type | Circuit Breaker |
Poles | 3P |
[In] Rated Current | 160 A at 40 °C |
IP Degree of Protection | IP40 |