HR 1234W is specially designed for high efficient discharge application. Its characteristics are small volume, light weight and high discharge efficiency. It can be used up to 5 yeas in standby service.
Specifications:
Cells Per Unit |
6 |
Voltage Per Unit |
12 V |
Capacity |
34W @ 15 minute-rate to 1.67V per cell @ 25°C (77°F) |
Maximum Discharge current |
100/130A (5sec.) |
Internal Resistance |
Approx. 19mΩ |
Operating Temperature Range |
Discharge:-15℃~50℃(5°F~122°F) |
Charge:-15℃~40℃(5°F~104°F) |
|
Storage:-15℃~40℃(5°F~104°F) |
|
Nominal Operating Temperature Range |
25°C ± 3°C (77°F ± 5°F) |
Float charging voltage |
13.5 to 13.8 VDC/unit Average at 25°C (77°F) |
Recommended Maximum Charging current limit |
3.4A |
Equalization and Cycle Service |
14.4 to 15.0 VDC/unit Average at 25°C (77°F) |
Self Discharge |
It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25℃ |
Terminal |
F2-Faston Tab250 |
Container Material |
ABS(UL94-HB) & Flammability resistance of(UL94-V0) can be available upon request. |