HR 1221W is specially designed for high efficient discharge application. Its characteristics are small volume, light weight and high discharge efficiency. It can be used up to 5 yeas in standby service.
Specifications:
Cells Per Unit |
6 |
Voltage Per Unit |
12 V |
Capacity |
21W @ 15 minute-rate to 1.67V per cell @ 25°C (77°F) |
Maximum Discharge current |
60/90A (5sec.) |
Internal Resistance |
Approx. 23.0mΩ |
Operating Temperature Range |
Discharge:-15℃~50℃(5°F~122°F) |
Charge:-15℃~40℃(5°F~104°F) |
|
Storage:-15℃~40℃(5°F~104°F) |
|
Nominal Operating Temperature Range |
25°C ± 3°C (77°F ± 5°F) |
Float charging voltage |
13.5 to 13.8 VDC/unit Average at 25°C (77°F) |
Recommended Maximum Charging current limit |
2.1A |
Equalization and Cycle Service |
14.4 to 15.0 VDC/unit Average at 25°C (77°F) |
Self Discharge |
It should be more than 75% of the capacity that before storage after stocked for 6 months at ambient temp. 25℃ |
Terminal |
F1/F2-Faston Tab187/250 |
Container Material |