Residual current protection relay, Vigirex RH21M, 30 mA or 300 mA,220/240 VAC 50/60 Hz,DIN rail mounting

In stock
SKU
56163
Special Price EGP 23,723 Regular Price EGP 35,944

Description

The RH21M Earth Leakage Relay is a critical component for electrical safety and protection. It is designed to detect and respond to earth leakage faults in electrical circuits. With a sensitivity of 300 mA and a response time of 0.06 seconds, it provides quick and reliable protection.

 

Key Features:

Sensitivity: With a 300 mA sensitivity, it can detect low-level earth leakage faults, preventing electrical hazards.

Fast Response: The relay responds in just 0.06 seconds, minimizing the impact of electrical faults.

Voltage Compatibility: Designed for use with 240 V electrical systems.

Reliable Protection: Provides effective protection against earth leakage faults, ensuring the safety of people and property.

 

The RH21M Earth Leakage Relay is an essential component for preventing electrical hazards and is crucial for ensuring the safety of electrical installations. Schneider Electric's reputation for reliability and performance makes this relay a dependable choice for a wide range of applications.

 

Specifications  

Main

 
Range VigiPacT
device short name RH99M
Product or component type Residual current protection relay
Relay application Protection relay
mounting support DIN rail
Earth-leakage protection class Type A
Type of setting Selector
Residual earth-leakage sensitity adjustment type Adjustable 9 settings
Earth-leakage sensitivity 0.03…30 A
Earth-leakage time delay Instantaneous for 0.03 A
  Adjustable 9 settings 0…4.5 s for 0.03…30 A
Current sensors compatibility VigiPacT TOA earth leakage current sensor
  VigiPacT A earth leakage current sensor
  VigiPacT L earth leakage current sensor
[Ithe] conventional enclosed thermal current 8:00 AM
Minimum load 10 mA at 12 V
[Us] rated supply voltage 380...415 V AC 50/60 Hz 55...110 %
Power consumption in VA 4 VA
Monitored distribution system 1000 V - AC at 50/60 Hz (maximum)
  1000 V - AC at 400 Hz (maximum)
Earthing system TT
  IT
  TN-S
[Uimp] rated impulse withstand voltage 8 kV
Reset Manual reset
Complementary  
Test function Local
  Remote test
Monitoring Electronics (continuous)
  Power supply (continuous)
  Relay/sensor link (continuous)
Type of measurement Earth fault current internal measurement, range: 80...100 %
Tamperproof of settings Protected by sealable cover
Connections - terminals Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
  Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12
  Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
  Fault: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
  Fault: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12
  Fault: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
  Relay test and fault reset: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16
  Relay test and fault reset: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16
  Relay test and fault reset: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16
  Sensor: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16
  Sensor: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16
  Sensor: screw terminal cable(s) 0.25…0.5 mm² flexible AWG 26...AWG 16
  Voltage presence: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12
  Voltage presence: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12
  Voltage presence: screw terminal cable(s) 0.25…2.5 mm² flexible AWG 24...AWG 12
Wire stripping length Auxiliary power supply: 7 mm for top connection
  Fault: 8 mm for bottom connection
  Relay test and fault reset: 5 mm for bottom connection
  Sensor: 5 mm for top connection
  Voltage presence: 8 mm for bottom connection
Tightening torque Auxiliary power supply: 0.6 N.m top
  Fault: 0.6 N.m bottom
  Relay test and fault reset: 0.25 N.m bottom
  Sensor: 0.25 N.m top
  Voltage presence: 0.6 N.m bottom
9 mm pitches 6
Width 54 mm
height 81 mm
Depth 74 mm
Net weight 0.3 kg
IP degree of protection IP40 on front face: conforming to EN/IEC 60529
  IP30 on side parts: conforming to EN/IEC 60529
  IP20 on connection terminals: conforming to EN/IEC 60529
IK degree of protection IK07 conforming to EN 50102
Mechanical robustness Fire resistance conforming to IEC 60695-2-1
  IK protection 2 joules: IK07 conforming to EN 50102
  Vibrations 13.2...100 Hz: 0.7 g
  Vibrations 2...13.2 Hz: +/- 1 mm
Environment  
Overvoltage category IV
Electrical shock protection class Class II
Electromagnetic compatibility Conducted and radiated emissions: , B, conforming to CISPR 11
  Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6
  Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2
  High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5
  Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4
  Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Relative humidity 95 % at 55 °C

 

 

Specifications

More Information
Weight 0.310000
Brand Schneider Electric
Model 56163
Depth [cm] 7.4
Width [cm] 5.4
Height [cm] 8.1
Range CCB others
Family PPCCB

Reviews

You're reviewing:

Residual current protection relay, Vigirex RH21M, 30 mA or 300 mA,220/240 VAC 50/60 Hz,DIN rail mounting