This Acti9 iCT is a modular contactor. It is a 2P remote control device with 2 normally open contacts. The rated current is 40A for AC-7a and 15A for AC-7b. The Ue rated operational voltage is 250VAC. The Uc control voltage is 220VAC to 240VAC. This device could be used for control circuits. This device could be used for remote switching lighting loads, small motors (fans, mixers) or HVAC system applications. It is compatible with all the Acti9 control auxiliaries, for lighting, heating & ventilation control applications.
Specifications:
Main |
|
range of product |
Acti9 |
Product name |
Acti9 iCT |
product or component type |
Contactor |
Device short name |
iCT |
Device application |
Motor-heating-lighting |
Poles |
2P |
[Ie] rated operational current |
40 A AC-7A |
15 A AC-7B |
|
Pole contact composition |
2 NO |
Network type |
AC |
Control type |
Remote control |
[Uc] control circuit voltage |
220...240 V AC 50 Hz |
Complementary |
|
Network frequency |
50 Hz |
[Ue] rated operational voltage |
250 V AC 50 Hz |
Maximum power |
1.6 W at 250 V AC |
[Ui] rated insulation voltage |
500 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage |
4 kV |
Control signal type |
Maintained |
Switching frequency |
100 switching operations/day |
local signalling |
Action indicator |
Hold-in power consumption in VA |
4.6 VA |
Inrush power in VA |
34 VA |
mounting mode |
Clip-on |
mounting support |
35 mm symmetrical DIN rail |
9 mm pitches |
4 |
Height |
85 mm |
Width |
36 mm |
Depth |
60 mm |
Colour |
White |
Mechanical durability |
1000000 cycles |
Electrical durability |
100000 cycles IEC/EN 61095 40 A 50 Hz AC-7A |
30000 cycles IEC/EN 61095 15 A 50 Hz AC-7B |
|
30000 cycles IEC/EN 61095 50 Hz AC-7C |
|
100000 cycles EN/IEC 60947-4-1 50 Hz AC-1 |
|
30000 cycles EN/IEC 60947-4-1 50 Hz AC-3 |
|
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5a |
|
30000 cycles EN/IEC 60947-4-1 50 Hz AC-5b |
|
Connections - terminals |
Control circuit: tunnel type terminals2 cable(s) 1.5 mm² rigid |
Control circuit: tunnel type terminals1 cable(s) 1.5…2.5 mm² rigid |
|
Power circuit: tunnel type terminals1 cable(s) 6…16 mm² flexible |
|
Power circuit: tunnel type terminals1 cable(s) 6…25 mm² rigid |
|
Control circuit: tunnel type terminals2 cable(s) 1.5…2.5 mm² flexible |
|
Tightening torque |
Control circuit: 0.8 N.m |
Power circuit: 3.5 N.m |
|
Product compatibility |
IACTc |
IACTs |
|
IACTp |
|
IATEt |
|
Compatibility code |
ICT |
Market segment |
Small commercial |
Residential |
|
Environment |
|
Standards |
IEC/EN 61095 |
Noise level |
30 dB |
Heat dissipation |
1.6 W at 50/60 Hz |
IP degree of protection |
IP20 conforming to IEC 60529 |
IP40 (modular enclosure) conforming to IEC 60529 |
|
Pollution degree |
2 |
Tropicalisation |
2 conforming to EN 60947-4-1 |
2 conforming to EN 61095 |
|
2 conforming to IEC 1095 |
|
Relative humidity |
95 % at 55 °C |
Operating altitude |
2000 m |
Ambient air temperature for operation |
-5…60 °C |
Ambient air temperature for storage |
-40…70 °C |