Introducing the RE17LAMW On-Delay Timing Relay by Schneider Electric, a reliable and precise timing solution designed to meet the needs of various industrial applications.
This relay offers precise on-delay timing control for your operations, with a time delay range from 1 second to 100 hours.
Key Features:
Precise Timing: The RE17LAMW provides highly precise on-delay timing control, ensuring that your operations run with accuracy.
Wide Time Delay Range: With a time delay range from 1 second to 100 hours, this relay offers versatility to suit various timing requirements.
Solid-State Output: The solid-state output design ensures durability and reliability in industrial environments.
Voltage Compatibility: This relay is compatible with a wide voltage range of 24-240V AC/DC, making it adaptable to various voltage inputs.
Technical Specifications:
Timing Range: 1s - 100h
Voltage Compatibility: 24-240V AC/DC
Output Type: Solid State
Specifications
Main | |
Range of product | Harmony Timer Relays |
Product or component type | Single function relay |
Discrete output type | Solid state |
Width | 17.5 mm |
component name | RE17L |
Time delay type | Power on-delay |
Time delay range | 1...10 s |
10...100 h | |
6...60 s | |
0.1...1 s | |
1...10 min | |
6...60 min | |
1...10 h | |
Nominal output current | 0.7 A |
Complementary | |
Control type | Selector switch front panel |
[Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz |
Voltage range | 0.85...1.1 Us |
Supply frequency | 50...60 Hz +/- 5 % |
control signal pulse width | 0.05 s typical |
Insulation resistance | 100 MOhm at 500 V DC conforming to IEC 60664-1 |
[Uimp] rated impulse withstand voltage | 5 kV during 1.2/50 µs |
power on delay | 100 ms |
Connections - terminals | Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end |
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end | |
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end | |
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end | |
Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
Dielectric strength | 2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1 |
Housing material | Self-extinguishing |
Repeat accuracy | +/- 0.5 % conforming to IEC 61812-1 |
Temperature drift | +/- 0.05 %/°C |
Voltage drift | +/- 0.2 %/V |
Setting accuracy of time delay | +/- 10 % of full scale at 25 °C conforming to IEC 61812-1 |
Reset time | 350 ms on de-energisation typical |
On-load factor | 100% |
Power consumption in VA | 0…3 VA at 240 V AC |
Maximum power consumption in W | 1.5 W at 240 V DC |
Breaking capacity | 0.5 A AC/DC conforming to UL |
0.7 A AC/DC at 20 °C | |
operating frequency | 10 Hz |
Maximum output current | 20 A |
Minimum switching current | 10 mA |
Maximum leakage current | 5 mA |
Maximum switching voltage | 250 V AC/DC |
Maximum voltage drop | <4 V 3-wire |
<8 V 2-wire | |
Electrical durability | 100000000 cycles |
Marking | CE |
Creepage distance | 4 kV/3 conforming to IEC 60664-1 |
Safety reliability data | MTTFd = 353.8 years |
B10d = 320000 | |
Mounting position | Any position in relation to normal vertical mounting plane |
Mounting support | 35 mm DIN rail conforming to IEC 60715 |
Net weight | 0.068 kg |
Time delay type | A |
Functionality | On-delay timing |
Compatibility code | RE17 |
Environment | |
Immunity to microbreaks | 20 ms |
Derating factor | 5 mA/°C |
standards | 2004/108/EC |
IEC 61000-6-1 | |
2006/95/EC | |
IEC 61000-6-3 | |
IEC 61000-6-2 | |
IEC 61812-1 | |
IEC 61000-6-4 | |
product certifications | GL |
CSA | |
cULus | |
Ambient air temperature for storage | -30…60 °C |
Ambient air temperature for operation | -20…60 °C |
IP degree of protection | IP20 (terminal block) conforming to IEC 60529 |
IP40 (housing) conforming to IEC 60529 | |
IP50 (front panel) conforming to IEC 60529 | |
Vibration resistance | 20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6 |
Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
Relative humidity | 93 % without condensation conforming to IEC 60068-2-30 |
Electromagnetic compatibility | Electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC 61000-4-2 |
Electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC 61000-4-2 | |
Susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m, conforming to IEC 61000-4-3 | |
Electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV, conforming to IEC 61000-4-4 | |
Electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC 61000-4-4 | |
1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to IEC 61000-4-5 | |
1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to IEC 61000-4-5 | |
Conducted RF disturbances: (0.15...80 MHz), level 3, 10 V, conforming to IEC 61000-4-6 | |
Voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC 61000-4-11 | |
Voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC 61000-4-11 | |
Conducted and radiated emissions: , class B, conforming to EN 55022 |