Modular Timing Relay - 8A - 0.3s to 30s - 2 CO (Changeover) - Star-Delta - 24V DC/24-240V AC/DC, Schneider Electric

Out of stock
SKU
RE22R2QEMR
Special Price EGP 2,111 Regular Price EGP 3,639

Description

Introducing the RE22R2QEMR Modular Timing Relay by Schneider Electric, a versatile and precise timing solution designed to meet the demands of various industrial applications.

This relay provides reliable timing control for your operations, offering a time delay range from 0.3 seconds to 30 seconds.

 

Key Features:

Modular Design: The modular design of the RE22R2QEMR ensures easy installation and integration into your control systems.

Wide Time Delay Range: With a time delay range from 0.3 seconds to 30 seconds, this relay offers flexibility to suit a wide range of timing requirements.

2 CO (Changeover) Contacts: Equipped with 2 changeover contacts, it allows you to switch between different circuits or devices with ease.

Voltage Compatibility: This relay is compatible with both 24V DC and a wide range of 24-240V AC/DC, making it adaptable to various voltage inputs.

Star-Delta Functionality: The star-delta function adds versatility to your timing control, providing an essential tool for motor control applications.

 

Technical Specifications:

Timing Range: 0.3s - 30s

Contact Configuration: 2 CO (Changeover) Contacts

Voltage Compatibility: 24V DC, 24-240V AC/DC

 

Specifications

Main
Range of product Harmony Timer Relays
Product or component type Single function relay
Discrete output type Relay
Device short name RE22
Nominal output current 08:00 ص
Complementary
Contacts type and composition 2 C/O timed contact, cadmium free
Time delay type Star-delta
Time delay range 0.3...30 s
Control type Rotary knob
Diagnostic button
[Us] rated supply voltage 24...240 V AC/DC 50/60 Hz
Release input voltage <= 2.4 V
Voltage range 0.85...1.1 Us
Supply frequency 50...60 Hz +/- 5 %
Connections - terminals Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque 0.6…1 N.m conforming to IEC 60947-1
Housing material Self-extinguishing
Repeat accuracy +/- 0.5 % conforming to IEC 61812-1
Temperature drift +/- 0.05 %/°C
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Insulation resistance 100 MOhm at 500 V DC conforming to IEC 60664-1
Recovery time 120 ms on de-energisation
Immunity to microbreaks 10 ms
Power consumption in VA 3 VA at 240 V AC
Power consumption in W 1.5 W at 240 V DC
Switching capacity in VA 2000 VA
Minimum switching current 10 mA at 5 V DC
Maximum switching current 08:00 ص
Maximum switching voltage 250 V AC
Electrical durability 100000 cycles, 8 A at 250 V, AC-1
100000 cycles, 2 A at 24 V, DC-1
Mechanical durability 10000000 cycles
Rated impulse withstand voltage 5 kV for 1.2…50 µs conforming to IEC 60664-1
Power on delay 100 ms
Creepage distance 4 kV/3 conforming to IEC 60664-1
Overvoltage category III conforming to IEC 60664-1
Safety reliability data B10d = 320000
MTTFd = 353.8 years
Mounting position Any position
Mounting support 35 mm DIN rail conforming to IEC 60715
Status LED LED backlight green (steady) for dial pointer indication
LED yellow (steady) for output relay energised
LED yellow (fast flashing) for timing in progress and output relay de-energised
LED yellow (slow flashing) for timing in progress and output relay energised
Width 22.5 mm
Net weight 0.09 kg
Environment
Dielectric strength 2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation conforming to IEC 61812-1
standards IEC 61812-1
UL 508
Directives 2006/95/EC - low voltage directive
2004/108/EC - electromagnetic compatibility
product certifications CE
CSA
GL
EAC
UL
RCM
CCC
Ambient air temperature for operation -20…60 °C
Ambient air temperature for storage -40…70 °C
IP degree of protection IP40 housing: conforming to IEC 60529
IP20 terminals: conforming to IEC 60529
IP50 front panel: conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Vibration resistance 20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn not operating for 11 ms conforming to IEC 60068-2-27
5 gn in operation for 11 ms conforming to IEC 60068-2-27
Relative humidity 95 % at 25…55 °C
Electromagnetic compatibility Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4
Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1 GHz) conforming to IEC 61000-4-3
Conducted RF disturbances - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6
Fast transient bursts - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4
Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11

Specifications

More Information
Weight 0.090000
Brand Schneider Electric
Model RE22R2QEMR
Width [cm] 2.25
Range Zelio Timers
Family IDSIG

Reviews