Introducing the Schneider Electric TM3DQ8R Modicon TM3 8-Relay Outputs, a versatile and reliable solution for your industrial automation needs. This module is designed to provide precise control and automation with eight relay outputs, making it ideal for a wide range of applications.
Key Features:
Versatile Control: The TM3DQ8R offers eight relay outputs, allowing you to control multiple devices with ease.
Screw Terminals: Screw terminals simplify installation and ensure a secure connection.
24V DC: This module operates at 24V DC, making it suitable for various industrial setups.
Technical Specifications:
Relay Outputs: 8
Terminals: Screw Terminals
Voltage: 24V DC
Specifications
Main | |
Range of product | Modicon TM3 |
Product or component type | Discrete output module |
range compatibility | Modicon M241 |
Modicon M251 | |
Modicon M221 | |
Modicon M262 | |
Discrete output type | Relay normally open |
Discrete output number | 8 |
discrete output logic | Positive or negative |
Discrete output voltage | 24 V DC for relay output |
240 V AC | |
Discrete output current | 2000 mA for relay output |
Complementary | |
Discrete I/O number | 8 |
Current consumption | 5 mA at 5 V DC via bus connector (at state off) |
0 mA at 24 V DC via bus connector (at state off) | |
40 mA at 24 V DC via bus connector (at state on) | |
30 mA at 5 V DC via bus connector (at state on) | |
Response time | 10 ms (turn-on) |
5 ms (turn-off) | |
Mechanical durability | 20000000 cycles |
Minimum load | 10 mA at 5 V DC for relay output |
Local signalling | 1 LED per channel (green) for output status |
Electrical connection | 11 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for outputs |
Maximum cable distance between devices | Unshielded cable: <30 m for relay output |
Insulation | Between output and internal logic at 2300 V AC |
Between outputs at 750 V AC | |
Between output groups at 1500 V AC | |
Marking | CE |
Mounting support | Top hat type TH35-15 rail conforming to IEC 60715 |
Top hat type TH35-7.5 rail conforming to IEC 60715 | |
plate or panel with fixing kit | |
height | 90 mm |
Depth | 84.6 mm |
Width | 27.4 mm |
Net weight | 0.11 kg |
Environment | |
standards | EN/IEC 61131-2 |
product certifications | CE |
cULus | |
UKCA | |
RCM | |
EAC | |
cULus HazLoc | |
Resistance to electrostatic discharge | 8 kV in air conforming to EN/IEC 61000-4-2 |
4 kV on contact conforming to EN/IEC 61000-4-2 | |
Resistance to electromagnetic fields | 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3 |
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 | |
1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3 | |
Resistance to magnetic fields | 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8 |
Resistance to fast transients | 2 kV for relay output conforming to EN/IEC 61000-4-4 |
Surge withstand | 1 kV I/O common mode conforming to EN/IEC 61000-4-5 DC |
Resistance to conducted disturbances | 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 |
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) | |
Electromagnetic emission | Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 |
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011 | |
Ambient air temperature for operation | -10…35 °C vertical installation |
-10…55 °C horizontal installation | |
Ambient air temperature for storage | -25…70 °C |
Relative humidity | 10…95 %, without condensation (in operation) |
10…95 %, without condensation (in storage) | |
IP degree of protection | IP20 with protective cover in place |
Pollution degree | 2 |
Operating altitude | 0...2000 m |
Storage altitude | 0…3000 m |
Vibration resistance | 3.5 mm at 5…8.4 Hz on DIN rail |
3 gn at 8.4…150 Hz on DIN rail | |
3.5 mm at 5…8.4 Hz on panel | |
3 gn at 8.4…150 Hz on panel | |
Shock resistance | 15 gn for 11 ms |