Schneider Electric presents the RM17TG00 Harmony Control Relay, designed to provide efficient control and monitoring of three-phase power sources in industrial applications.
This control relay is engineered to offer high responsiveness and reliable performance in managing three-phase currents.
Key Features:
Three-Phase Control Relay: The RM17TG00 allows for straightforward control and monitoring of three-phase power sources, enhancing operational efficiency.
1CO (1 Changeover) Contact: Equipped with a single set of changeover contacts, it offers precision in power source control.
Wide Voltage Range: Covering a voltage range from 208 to 480 volts AC, this control relay is versatile and suitable for diverse industrial applications.
Technical Specifications:
Voltage Range: 208-480V AC
Number of Contacts (CO): 1
Specifications
Main | |
Range of product | Harmony Control Relays |
Product or component type | 3-phase control relay |
Relay type | Control relay |
Product specific application | For 3-phase supply |
Relay name | RM17TG |
Relay monitored parameters | Phase sequence |
Phase failure detection (2 or more phase cut) | |
time delay | Without |
Switching capacity in VA | 1250 VA |
Measurement range | 208...480 V voltage AC |
Contacts type and composition | 1 C/O |
[Uc] control circuit voltage | 208...480 V |
Complementary | |
Maximum switching voltage | 250 V AC |
250 V DC | |
Minimum switching current | 10 mA at 5 V DC |
Supply voltage limits | 183…528 V AC |
Control circuit voltage limits | - 12 % + 10 % Un |
Power consumption in VA | 0…22 VA at 400 V AC 50 Hz |
Voltage detection threshold | < 100 V AC |
control circuit frequency | 50...60 Hz +/- 10 % |
Output contacts | 1 C/O |
Nominal output current | 05:00 ص |
Measurement voltage limits | 183…528 V AC |
delay at power up | 650 ms |
Voltage range | 183...528 V |
Response time | <= 130 ms (in the event of a fault) |
Marking | CE |
Overvoltage category | III conforming to IEC 60664-1 |
Insulation resistance | > 500 MOhm at 500 V DC conforming to IEC 60255-5 |
> 500 MOhm at 500 V DC conforming to IEC 60664-1 | |
[Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
Supply frequency | 50/60 Hz +/- 10 % |
Operating position | Any position without derating |
Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end |
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end | |
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end | |
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end | |
Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
Housing material | Self-extinguishing plastic |
Local signalling | LED (yellow) for relay ON |
Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
Electrical durability | 100000 cycles |
Mechanical durability | 30000000 cycles |
Operating rate | <= 360 operations/hour full load |
Utilisation category | AC-12 conforming to IEC 60947-5-1 |
AC-13 conforming to IEC 60947-5-1 | |
AC-14 conforming to IEC 60947-5-1 | |
AC-15 conforming to IEC 60947-5-1 | |
DC-12 conforming to IEC 60947-5-1 | |
DC-13 conforming to IEC 60947-5-1 | |
Safety reliability data | MTTFd = 924.6 years |
B10d = 850000 | |
Width | 17.5 mm |
Net weight | 0.13 kg |
Environment | |
Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4 |
Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 | |
Immunity for industrial environments conforming to IEC 61000-6-2 | |
standards | IEC 60255-1 |
product certifications | C-Tick |
GL | |
CSA | |
UL | |
GOST | |
Directives | 73/23/EEC - low voltage directive |
89/336/EEC - electromagnetic compatibility | |
Ambient air temperature for storage | -40…70 °C |
Ambient air temperature for operation | -20…50 °C |
Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
Vibration resistance | 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6 |
1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1 | |
Shock resistance | 15 gn for 11 ms conforming to IEC 60255-21-1 |
IP degree of protection | IP20 (terminals) conforming to IEC 60529 |
IP30 (casing) conforming to IEC 60529 | |
Pollution degree | 3 conforming to IEC 60664-1 |
Dielectric test voltage | 2 kV, 1 min AC 50 Hz |
Non-dissipating shock wave | 4 kV |