Enhance the performance and control of your electrical systems with the Schneider Electric LC1E2510M5 EasyPact TVS Contactor. This 3-pole contactor features a 3 NO (3 normally open) configuration, designed to handle AC3 applications at 440V and 25A. The 220V AC coil, operating at 50Hz, ensures reliable and efficient control, making it a versatile choice for various industrial applications. Additionally, it comes equipped with 1 NO (1 normally open) auxiliary contact for added versatility in control and monitoring.
Key Features:
3P 3 NO Configuration: This contactor is equipped with 3 normally open contacts, providing versatile switching and control options.
AC3 Rating: With a 440V AC3 rating, it's capable of handling high-voltage applications efficiently.
Reliable Coil: The 220V AC coil operates at 50Hz, ensuring dependable and consistent operation.
Auxiliary Contact: Includes 1 NO auxiliary contact for expanded control and monitoring capabilities.
Technical Specifications:
Pole Configuration: 3P (3-Pole)
Contacts: 3 NO (Normally Open)
AC3 Rating: 440V, 25A
Coil Voltage: 220V AC, 50Hz
Auxiliary Contact: 1 NO (Normally Open)
Upgrade your electrical systems with the Schneider Electric LC1E2510M5 EasyPact TVS Contactor for dependable and efficient control in demanding industrial settings.
Specifications
Main | |
Range | Easy TeSys |
Range of product | Easy TeSys Control |
Product or component type | Contactor |
Device short name | LC1E |
contactor application | Motor control |
Resistive load | |
utilisation category | AC-1 |
AC-3 | |
Poles description | 3P |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
[Ie] rated operational current | 25 A (at <55 °C) at <= 440 V AC AC-3 for power circuit |
36 A (at <55 °C) at <= 440 V AC AC-1 for power circuit | |
[Uc] control circuit voltage | 220 V AC 50 Hz |
Complementary | |
Motor power kW | 5.5 kW at 220...230 V AC 50/60 Hz |
11 kW at 380...400 V | |
11 kW at 415 V | |
11 kW at 440 V | |
15 kW at 500 V | |
15 kW at 660...690 V | |
Pole contact composition | 3 NO |
[Ith] conventional free air thermal current | 36 A (at 55 °C) |
Irms rated making capacity | 250 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
Rated breaking capacity | 200 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 240 A 40 °C - 10 s for power circuit |
120 A 40 °C - 60 s for power circuit | |
50 A 40 °C - 600 s for power circuit | |
Associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1 |
40 A gG at <= 690 V coordination type 1 for power circuit | |
Average impedance | 2.5 mOhm - Ith 36 A 50 Hz for power circuit |
Power dissipation per pole | 1.6 W AC-3 |
3.2 W AC-1 | |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
Overvoltage category | III |
Pollution degree | 3 |
[Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
Mechanical durability | 10000000 cycles |
Electrical durability | 350000 cycles AC-1 |
300000 cycles AC-3 | |
Control circuit type | AC at 50 Hz |
Control circuit voltage limits | 0.85...1.1 Uc (55 °C):operational 50 Hz |
0.3...0.6 Uc (55 °C):drop-out 50 Hz | |
Inrush power in VA | 95 VA 50 Hz cos phi 0.75 (at 20 °C) |
95 VA 60 Hz cos phi 0.75 (at 20 °C) | |
Hold-in power consumption in VA | 8.3 VA 50 Hz cos phi 0.3 (at 20 °C) |
8.5 VA 60 Hz cos phi 0.3 (at 20 °C) | |
Heat dissipation | 2…3 W for control circuit |
Operating time | 12...22 ms on closing |
4...19 ms on opening | |
Maximum operating rate | 1800 cyc/h 60 °C |
Connections - terminals | Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end |
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end | |
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end | |
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end | |
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end | |
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end | |
Power circuit: screw clamp terminals 1 1.5…6 mm² - cable stiffness: solid without cable end | |
Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: solid without cable end | |
Power circuit: screw clamp terminals 1 1…6 mm² - cable stiffness: flexible with cable end | |
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end | |
Tightening torque | Control circuit: 1.2 N.m |
Power circuit: 1.5 N.m | |
Auxiliary contact composition | 1 NO |
Minimum switching voltage | 17 V for control circuit |
Minimum switching current | 5 mA for control circuit |
Insulation resistance | > 10 MOhm for control circuit |
Non-overlap time | 1.5 ms on energisation guaranteed between NC and NO contact |
1.5 ms on de-energisation guaranteed between NC and NO contact | |
mounting support | Plate |
DIN rail | |
Environment | |
Standards | IEC 60947-1 |
IEC 60947-4-1 | |
IEC 60947-5-1 | |
product certifications | EAC |
CE | |
IP degree of protection | IP2X conforming to IEC 60529 |
Protective treatment | TH (pollution degree 3) conforming to IEC 60068-2-30 test Db |
Permissible ambient air temperature around the device | -20…70 °C at Uc |
-60…80 °C storage | |
-5…55 °C operation | |
Operating altitude | 3000 m without derating |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Mechanical robustness | Vibrations contactor open (1.5 Gn, 5...300 Hz) |
Vibrations contactor closed (3 Gn, 5...300 Hz) | |
Shocks contactor closed (10 Gn for 11 ms) | |
Shocks contactor open (6 Gn for 11 ms) | |
height | 74 mm |
Width | 45 mm |
Depth | 85 mm |
Net weight | 0.36 kg |