The Schneider Electric LC1E1201M5 Contactor is a reliable and high-performance electrical contactor designed for a wide range of applications. This 3P (3 Pole) contactor features 3 Normally Open (NO) main contacts suitable for AC-3 applications at 440V and 12A. It operates with a 220V AC coil at 50Hz and includes an additional 1 Normally Closed (NC) auxiliary contact for enhanced control.
Key Features:
Versatile Contact Arrangement: With 3 NO main contacts, this contactor is suitable for various AC-3 applications at 440V and 12A.
Auxiliary Contact: The included 1 NC auxiliary contact provides additional control options for your electrical systems.
Durable Construction: Built to last with high-quality materials and craftsmanship, ensuring long-term reliability.
Technical Specifications:
Contactor Type: 3P (3 Pole), 3NO (Normally Open)
Rated Current (AC-3): 12A
Rated Voltage (AC-3): 440V
Coil Voltage: 220V AC, 50Hz
Auxiliary Contact: 1 NC (Normally Closed)
The Schneider Electric LC1E1201M5 Contactor is a top choice for controlling electrical circuits and is engineered to provide dependable performance in demanding environments.
Specifications
Main | |
Range | Easy TeSys |
Range of product | Easy TeSys Control |
Product or component type | Contactor |
Device short name | LC1E |
contactor application | Resistive load |
Motor control | |
utilisation category | AC-3 |
AC-1 | |
Poles description | 3P |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
[Ie] rated operational current | 25 A (at <55 °C) at <= 440 V AC AC-1 for power circuit |
12 A (at <55 °C) at <= 440 V AC AC-3 for power circuit | |
[Uc] control circuit voltage | 220 V AC 50 Hz |
Complementary | |
Motor power kW | 3 kW at 220...230 V AC 50/60 Hz (AC-3) |
5.5 kW at 380...400 V AC 50/60 Hz (AC-3) | |
5.5 kW at 415 V AC 50/60 Hz (AC-3) | |
5.5 kW at 440 V AC 50/60 Hz (AC-3) | |
7.5 kW at 500 V AC 50/60 Hz (AC-3) | |
7.5 kW at 660...690 V AC 50/60 Hz (AC-3) | |
Pole contact composition | 3 NO |
[Ith] conventional free air thermal current | 25 A (at 55 °C) for power circuit |
Irms rated making capacity | 120 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
Rated breaking capacity | 96 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 105 A 40 °C - 10 s for power circuit |
61 A 40 °C - 60 s for power circuit | |
30 A 40 °C - 600 s for power circuit | |
Associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1 |
25 A gG at <= 690 V coordination type 1 for power circuit | |
Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
Power dissipation per pole | 0.36 W AC-3 |
1.6 W AC-1 | |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
Overvoltage category | III |
Pollution degree | 3 |
[Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
Mechanical durability | 10000000 cycles |
Electrical durability | 1400000 cycles AC-3 |
300000 cycles AC-1 | |
Control circuit type | AC at 50 Hz |
Control circuit voltage limits | 0.85...1.1 Uc (55 °C):operational 50 Hz |
0.3...0.6 Uc (55 °C):drop-out 50 Hz | |
Inrush power in VA | 95 VA 50 Hz cos phi 0.75 (at 20 °C) |
95 VA 60 Hz cos phi 0.75 (at 20 °C) | |
Hold-in power consumption in VA | 8.3 VA 50 Hz cos phi 0.3 (at 20 °C) |
8.5 VA 60 Hz cos phi 0.3 (at 20 °C) | |
Heat dissipation | 2…3 W for control circuit |
Operating time | 12...22 ms on closing |
4...19 ms on opening | |
Maximum operating rate | 1800 cyc/h 60 °C |
Connections - terminals | Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end |
Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end | |
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end | |
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end | |
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end | |
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end | |
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end | |
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end | |
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end | |
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end | |
Tightening torque | Power circuit: 1.2 N.m |
Control circuit: 1.2 N.m | |
Auxiliary contact composition | 1 NC |
Minimum switching voltage | 17 V for control circuit |
Minimum switching current | 5 mA for control circuit |
Insulation resistance | > 10 MOhm for control circuit |
Non-overlap time | 1.5 ms on energisation guaranteed between NC and NO contact |
1.5 ms on de-energisation guaranteed between NC and NO contact | |
mounting support | Plate |
DIN rail | |
Environment | |
Standards | IEC 60947-4-1 |
IEC 60947-1 | |
IEC 60947-5-1 | |
product certifications | CE |
EAC | |
IP degree of protection | IP2X conforming to IEC 60529 |
Protective treatment | TH (pollution degree 3) conforming to IEC 60068-2-30 |
Permissible ambient air temperature around the device | -20…70 °C at Uc |
-60…80 °C storage | |
-5…55 °C operation | |
Operating altitude | 3000 m without derating |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Mechanical robustness | Vibrations contactor open (1.5 Gn, 5...300 Hz) |
Vibrations contactor closed (3 Gn, 5...300 Hz) | |
Shocks contactor open (7 Gn for 11 ms) | |
Shocks contactor closed (10 Gn for 11 ms) | |
height | 74 mm |
Width | 45 mm |
Depth | 80 mm |
Net weight | 0.3 kg |