Introducing the Schneider Electric Compact NSX100N Circuit Breaker, a high-performance solution for circuit protection.
Engineered to ensure the safety and efficiency of your electrical systems, this circuit breaker offers robust protection capabilities, making it suitable for a variety of applications.
Key Features:
High Breaking Capacity: With an impressive 50kA breaking capacity at 415VAC, this circuit breaker can handle fault currents, enhancing the safety of your electrical circuits.
3 Poles: The 3-pole configuration adds versatility to your electrical system, making it suitable for various applications and installations.
Micrologic 2.2 Trip Unit: Equipped with the advanced Micrologic 2.2 trip unit, this circuit breaker offers intelligent protection with enhanced features for precise fault detection and response.
40A Rating: The 40A rating allows this circuit breaker to handle moderate electrical loads while providing reliable protection.
Technical Specifications:
Breaking Capacity: 50kA at 415VAC
Poles: 3
Trip Unit Type: Micrologic 2.2
Current Rating: 40A
Specifications | |
Main |
|
Range | ComPacT new generation |
Product name | ComPacT NSX new generation |
device short name | NSX100N |
Product or component type | Circuit breaker |
Device application | Distribution |
Poles description | 3P |
Protected poles description | 3D |
[In] rated current | 40 A at 40 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
Network type | AC |
Network frequency | 50/60 Hz |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity | 90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 | |
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 | |
Performance level | N 50 kA 415 V AC |
Trip unit name | MicroLogic 2.2 |
Trip unit technology | Electronic |
Trip unit protection functions | LSoI |
control type | Toggle |
Circuit breaker mounting mode | Fixed |
Complementary | |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 8 kV |
[Ics] rated service short-circuit breaking capacity | 90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 | |
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 | |
Mechanical durability | 50000 cycles |
Electrical durability | 50000 cycles at 440 V In/2 |
30000 cycles at 440 V In | |
20000 cycles at 690 V In/2 | |
10000 cycles at 690 V In | |
Power dissipation per pole | 1.34 W |
mounting support | Backplate |
Mounting position | Horizontal and vertical |
Flat on the back | |
Upside connection | Front |
downside connection | Front |
Connection pitch | 35 mm |
Protection type | L : for overload protection (long time) |
So : for short time short-circuit protection with fixed delay | |
I : for instantaneous short-circuit protection | |
Trip unit rating | 40 A at 40 °C |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
[Ir] long-time protection pick-up adjustment range | 18...40 A |
Long-time protection delay adjustment type tr | Fixed |
[tr] long-time protection delay adjustment range | 400 s at 1.5 x Ir |
16 s at 6 x Ir | |
11 s at 7.2 x Ir | |
thermal memory | 20 minutes before and after tripping |
Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
[Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
Short-time protection delay adjustment type tsd | Fixed |
Instantaneous protection pick-up adjustment type Ii | Fixed |
[Ii] instantaneous protection pick-up adjustment range | 600 A |
earth-leakage protection | Without |
Zone selective interlocking ZSI | Without |
Number of slots for electrical auxiliaries | 5 slot(s) |
Local signalling | Flashing LED (green) for ready to operate |
LED 105 % Ir (red) for overload | |
LED 90 % Ir (orange) for overload | |
Width (W) | 105 mm |
Height (H) | 161 mm |
Depth (D) | 86 mm |
Net weight | 2.05 kg |
Environment | |
standards | EN/IEC 60947 |
product certifications | CCC |
EAC | |
Marine | |
Overvoltage category | Class II |
Electrical shock protection class | Class II |
Pollution degree | 3 conforming to IEC 60664-1 |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -50…85 °C |
Relative humidity | 0…95 % |
Operating altitude | 0...2000 m without derating |
2000 m...5000 m with derating |