Introducing the Schneider Electric Compact NSX100H Circuit Breaker, a dependable and high-performance solution for circuit protection. Engineered to ensure the safety and efficiency of your electrical systems, this circuit breaker offers robust protection capabilities, making it suitable for a variety of applications.
Key Features:
High Breaking Capacity: With an impressive 70kA breaking capacity at 415VAC, this circuit breaker can handle high fault currents, significantly enhancing the safety of your electrical circuits.
12.5A MA Trip Unit: Equipped with a 12.5A MA trip unit, this circuit breaker offers precise and adjustable protection settings, allowing you to tailor the breaker's response to your specific requirements.
3 Poles: With a 3-pole configuration, this circuit breaker is versatile and adaptable for various applications.
3D: The 3D designation signifies its compatibility with a range of tripping units, ensuring flexible protection options.
Technical Specifications:
Breaking Capacity: 70kA at 415VAC
MA Trip Unit Rating: 12.5A
Poles: 3
Tripping Units Compatibility: 3D
Specifications | |
Main |
|
Range | ComPact |
Product name | ComPact NSX |
Range of product | ComPact NSX100...250 |
device short name | NSX100H |
Product or component type | Circuit breaker |
Device application | Motor |
Number of poles | 3P |
Protected poles description | 3t |
[In] rated current | 12.5 A at 65 °C |
[Ue] rated operational voltage | 690 V AC 50/60 Hz |
Network type | AC |
Network frequency | 50/60 Hz |
Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
utilisation category | Category A |
[Icu] rated ultimate short-circuit breaking capacity | 10 kA at 600 V AC 50/60 Hz conforming to UL 508 |
85 kA at 240 V AC 50/60 Hz conforming to UL 508 | |
65 kA at 480 V AC 50/60 Hz conforming to UL 508 | |
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 | |
100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 | |
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 | |
50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
Performance level | H 70 kA 415 V AC |
Trip unit name | MA |
Trip unit technology | Magnetic |
Trip unit protection functions | I |
control type | Toggle |
Circuit breaker mounting mode | Fixed |
Complementary | |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz |
[Uimp] rated impulse withstand voltage | 8 kV |
[Ics] rated service short-circuit breaking capacity | 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 | |
35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 | |
50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 | |
70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 | |
Mechanical durability | 50000 cycles |
Electrical durability | 10000 cycles at 690 V In |
20000 cycles at 690 V In/2 | |
30000 cycles at 440 V In | |
50000 cycles at 440 V In/2 | |
mounting support | Backplate |
Upside connection | Front |
downside connection | Front |
Connection pitch | 35 mm |
Protection type | I : for short-circuit protection (magnetic) |
Trip unit rating | 12.5 A at 65 °C |
Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
[Isd] Short-time protection pick-up adjustment range | 6...14 x In |
earth-leakage protection | Without |
Number of slots for electrical auxiliaries | 5 slot(s) |
Width (W) | 105 mm |
Height (H) | 161 mm |
Depth (D) | 86 mm |
Net weight | 2.05 kg |
Environment | |
standards | EN/IEC 60947 |
product certifications | CCC |
EAC | |
Marine | |
Overvoltage category | Class II |
Electrical shock protection class | Class II |
Pollution degree | 3 conforming to IEC 60664-1 |
IP degree of protection | IP40 conforming to IEC 60529 |
IK degree of protection | IK07 conforming to IEC 62262 |
Ambient air temperature for operation | -25…70 °C |
Ambient air temperature for storage | -50…85 °C |
Relative humidity | 0…95 % |
Operating altitude | 0...2000 m without derating |
2000 m...5000 m with derating |